- Chịu được nhiệt độ lên đến 2850C  
- Chiều dài có thể cắt theo yêu cầu  
- Đầu ra có thể lên tới 70W/m    
- Phạm vi điều khiển rộng, đầy đủ phụ kiện, tiêu chuẩn rộng
- Có sẵn loại  220 - 240V AC (110 - 120V AC on request)
- Ex
  • Thông tin sản phẩm
  • Bình luận

Quintherm IPH is a constant wattage heating tape that can be used for freeze protection or maintenance of process temperatures in pipework and vessels.
It can be cut-to-length at site and can replace mineral insulated cables for applications where the cut-to-length feature or field fabricated heating cable is preferred.
Quintherm IPH is approved for use in hazardous, safe and corrosive environments.
Because of the special construction with heating zones no additional cold lead is required. From cut point to the next heating wire bonding point the heating cable remains cold and serves as a cold lead.
The installation of IPH heating tape is quick and simple and requires few special skills and tools. Termination and power connection components are provided in convenient kits.

Options

IPH..C Nickel plated copper braid providing mechanical protection or where traced equipment does not provide an effective earth path.
IPH..NF Fluoropolymer jacket over nickel plated copper braid provides protection where corrosive chemical or vapours may be present.
Technical Data Maximum Pipe / Workpiece Temperature
Maximum Temperature: 300°C (Un - Energized)   The surface of the heater must not exceed the maximum withstand temperature of its constructional materials or the Temperature Classification (if installed in a hazardous area). This is ensured by limiting the pipe or workpiece temperature to a safe level either by design calculation (a Stabilised Design) or by means of temperature controls.
For worst case conditions, the temperature of steel pipes should be limited to the following levels:
Minimum Insallation Temperature: -40°C  
Temperature Classification see table right side  
Power Supply: 220-240V AC  
Weights and Dimension: Type Output (W/m) T6 T5 T4 T3 T2 T1 Non Ex
Type Nom Dimensions (mm) Weight Kg/100m Min. Bending radius (mm) Gland size
IPH.. 10

Not Approved

275
IPH… 8.8 x 6.0 12 25 M20 30 239
IPH…N 9,6 x 6,8 16 30 M20 50 192
IPH…NF 10.3 x 7,5 19 35 M20 70 133
Approvals IPH..N 10 44 61 102 180 275 275 275
Approval Certificate No. Standard   30     24 116 241 241 241
ATEX SIRA 02ATEX3078 EN60079-0:2009 50       48 190 190 190
EN60079-30-1:2007 70         129 129 129
IEC60079-31:2008 IPH..NF 10 40 60 105 186 275 275 275
CENELEC SCS Ex 94D3114 EN50014:1992 30     22 132 249 249 249
EN50019:1994 50       63 204 204 204
Approved for Zone 1 + 2 70         147 147 147
Construction Maximum Circuit Length
Heating Element: Nickel-Chromium   Max. Circuit Length Zone Length
Power Conductors: Nickel Plated Copper 2,5mm² Output (W/m) 115V 230V 115V 230V  
Conductor Insulation: Glass/Mica 10 79m 152m Contact us for detail
Primary Insulation Fluoropolymer (PFA) 30 46m 88m
Braid: Nickel Plated Copper 50 35m 68m
Over Jacket: Fluoropolymer (PFA) 70 30m 56m
Ordering Information Power Conversion Factors
  115V Heating Tape 230V Heating Tape  
277V Factor 5.80 277V Factor 1.45
230V Factor 4.00 240V Factor 1.09
208V Factor 3.27 220V Factor 0.91
120V Factor 1.09 208V Factor 0.82
110V Factor 0.91 115V Factor 0.25