Danh mục sản phẩm
- Tự động điều chỉnh lượng nhiệt tỏa để tăng hoặc giảm nhiệt độ đường ống | |||||||
- Sẽ không quá nhiệt hoặc cháy, thậm chí cả khi chồng chéo | |||||||
- Chiều dài có thể cắt theo yêu cầu | |||||||
- Phạm vi điều khiển rộng, đầy đủ phụ kiện, tiêu chuẩn rộng | |||||||
- Có sẵn loại 208 - 277V AC (110 - 120V AC on request) | |||||||
- Ex |
Quintherm ILHS is an industrial grade, self-regulating heating tape that can be used for applications ranging from process heating or maintenance of temperatures up to 200°C.
It can be cut to length on site and exact piping lengths can be matched without any complicated design considera- tions.
ILHS is approved for use in safe, hazardous and corrosive environments to world-wide standards.
Its self-regulating characteristics improve safety and relia- bility. ILHS will not overheat or burnout, even when over- lapped upon itself. Its power output is self-regulated in response to the pipe temperature.
The installation of Quintherm ILHS is quick and simple and requires no special skills or tools. Termination, splic- ing and power connection components are all provided in convenient kits.
Options
ILMw… | Basic heating tape without braiding and without outerjacket. | |||||
ILMw…C | Tinned copper braid providing mechanical protection or where traced equipment does not provide an effective earth path. eg. Plastic pipework | |||||
ILMw…CT | Thermoplastic outerjacket over tinned copper braid provides additional protection. | |||||
ILMw…CF | Fluoropolymer outerjacket over tinned copper braid provides protection where corrosive chemical solutions or vapours may be present. |
Technical Data | Max. Length (m) vs. Circuit Breaker Size | ||||||||
Max. Allowed Temperature: | 150°C (ON) | Type | Start Temp. | 16A | 20A | 32A | |||
200°C (OFF) | ILHS152.. | 10°C | 126 | 154 | - | ||||
Min. Installation Temperature: | -40°C | 0°C | 120 | 150 | - | ||||
Min. Operation Temperature: | -60°C | ILHS302.. | 10°C | 83 | 102 | 108 | |||
Power Supply: | 208-277V AC | 0°C | 77 | 98 | 102 | ||||
Protective Braiding: | ≤ 18,2Ohm/km | ILHS452.. | 10°C | 62 | 76 | 88 | |||
Temperature Classification: | T3(200°C) | 0°C | 58 | 72 | 82 | ||||
ILHS602.. | 10°C | 50 | 62 | 76 | |||||
0°C | 46 | 58 | 70 | ||||||
.-40 ̊C | 8 | 14 | 22 |
Approvals | Thermal Ratings | ||
Testing Authority | Certificate No. | Standards | Nominal output at 230V when ILHS is installed on insu- lated metal pipes. |
IECEx | SIR 12.0054 | IEC 60079 | W/m |
ATEX | Sira 12ATEX3136 | EN 60079 | ![]() |
Approval for Zone 1 + 2 | |||
Accessories | Ordering Information | ||
Quintex supply a complete range of accessories includ- ing termination/splice kits, end seals, junction boxes and controls. Such items carry separate approvals from the heating tapes. When used in hazardous areas, only use approved components. | ![]() |
![]() |
234/7 Vườn Lài, P. Phú Thọ Hòa,Q.Tân Phú, TP. Hồ Chi Minh |
![]() |
Tel: 028.3978.2976 - 0888.183.943 Fax: 028.3978.2977 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |
![]() |
P.602, S-Home Building, 110A Đường 30/4, Q. Hải Châu, Đà Nẵng |
![]() |
Tel: 023.6384.3554 Fax: 023.6384.3455 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |
![]() |
P.201, 63 Vũ Ngọc Phan, P. Láng Hạ, Q. Đống Đa, TP. Hà Nội |
![]() |
Tel: 024.3775.7157 Fax: 024.3775.7154 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |