CHỐNG SÉT LAN TRUYỀN ĐƯỜNG TRUYỀN DỮ LIỆU/TÍN HIỆU RS232,IMAX=20KA

Số liên lạc: (028).3978 2976 - 0888.183.943
Tiếng Việt Tiếng Anh
Số liên lạc:
(028).3978 2976 - 0888.183.943
CHỐNG SÉT LAN TRUYỀN ĐƯỜNG TRUYỀN DỮ LIỆU/TÍN HIỆU RS232,IMAX=20KA
Nhãn hiệu: Kumwell
Giá:
Liên hệ

Mã hàng: KSMH.SG

Xuất xứ: Thái Lan

  • Thông tin sản phẩm
  • Bình luận

Kumwell KSMH.SG series of surge peotective devices has been developed to protect againts the effects of induced voltages onto data, signal and communication.

It is intended forthose applicatios where high ground potential rises may frequency occur, such as in location close to electric railways.

The circuit topology consists of amulti- stage protector providing both commom (longitudinal) mode and differential (transverse) mode protection.

Coarse protection is provided by a three teminal GDT while fine protection is provided using a high speed silicon avanlanche diodes or metal oxide varistor stage.

Type

Technical Data

KSMH.SG-xxxV

5V

12V

15V

24V

30V

48V

60V

110V

Electrical Data

Lines protected

 

1(2 conductors)

Nominal operating voltage (DC)

Un

5V

12V

15V

24V

30V

48V

60V

110V

Max. continuous operating voltage (DC)

UC

6V

15V

18V

28V

33V

52V

64V

170V

Rated load current at 25°C

IL

1A

 Norminal discharge current (8/20µs)

In

10kA

Max. discharge current (8/20µs)

Imax

20kA

 Lightning impulse current (10/350µs)

Iimp

2.5kA

Residual voltage at 5kA (8/20µs)

Ures (line-line)

<22V

<42V

<48V

<70V

<80V

 

<140V

 

 

<160V

 

<450V

 

 

280-420V

Rated spark overvoltage

(SG-PG)

(a-b) (a,b-SG)

7-10V

16-19V

20-24V

30-36V

35-43V

56-58V

67-85V

184-264V

Response time of overvoltage protection


tA (a,b – SG)

(SG-PG)

 

<1ns

<100 ns

Thermal protection

 

Yes

Insulation resistance of the protection


Riso (a,b )

 

≥ 6kΩ

≥15MΩ

≥18MΩ

≥28MΩ

≥33MΩ

≥52MΩ

≥64MΩ

≥ 170MΩ

Serial resistance

R

1.6-2.0Ω

Transverse capacitance

C (a,b –SG)

(SG-PG).

50Pf

5pF

Cut-off frequency

fG

30MHz

Mechanical data

Temperature range

 

-40°C to + 80°C

Terminal cross section

 

Stranded to 4 mm2

Mounting

 

DIN rail 35mm

Degree of protection

 

IP20

 
Gọi ngay SMS Chỉ Đường Zalo
Zalo
Hotline: (028).3978 2976