Kumwell KZ01.DTE-L is a complex range of surge protection devices designed for protection of data, communication, measuring and control lines against surge effects. These surge protection devices are recommended for use in the Lightning Protection Zones Concept at the boundaries of LPZ 0A(B) - 1 according to IEC 62305. All types provide effect protection of connected equipment against common mode and differential mode surge effects according to IEC 61643-21. The rated load current of individual protected lines IL < 0.1 A.
These devices consist of gas discharge tubes, series impedance and transils. The number of protected pairs is optional (1-2). These devices are produced for nominal voltage within the range of 6V-170V. Maximum discharge current is 10 kA (8/20). For the protection of telephone lines it is recommended to use a type with nominal voltage UN = 170V (with code mark "T").
Type |
1 |
KZ01.DTE/1P.6-L |
KZ01.DTE/1P.12-L |
KZ01.DTE/1P.24-L |
|
Number of protected pairs |
2 |
KZ01.DTE/2P.6-L |
KZ01.DTE/2P.12-L |
KZ01.DTE/2P.24-L |
|
Nominal voltage |
UN |
6 V |
12 V |
24 V |
|
Max. continuous operating voltage |
UC |
7.2 V |
14.4 V |
28.6 V |
|
Rated load current |
IL |
100 mA |
|||
C2 Max. discharge current (8/20) |
Imax |
10 kA |
|||
C2 Nominal dischrge current (8/20) |
In |
1 kA |
|||
C2 Voltage protection level at In |
UP |
15 V |
28 V |
64 V |
|
C3 Voltage protection level at 1 kV/µs |
UP |
9 V |
18 V |
34 V |
|
Response time |
tA |
< 30 ns |
|||
Data rate |
|
1 MBit/s |
|||
Series impedance per line |
|
1.5 - 10 Ω |
|||
Parasitic capacitance |
C |
1.5 nF |
|||
Recommended cable cross-section |
|
0.25-1.5 mm2 |
|||
Category tested acc. To IEC 61643-21:2000 |
|
A2, B2, C2, C3, D1 |
|||
Type |
1 |
KZ01.DTE/1P.48-L |
KZ01.DTE/1P.T-L |
||
Number of protected pairs |
2 |
KZ01.DTE/2P.48-L |
KZ01.DTE/2P.T-L |
||
Nominal voltage |
UN |
48 V |
170 V |
||
Max. continuous operating voltage |
UC |
57.6 V |
204 V |
||
Rated load current |
IL |
100 mA |
|||
C2 Max. discharge current (8/20) |
Imax |
10 kA |
|||
C2 Nominal dischrge current (8/20) |
In |
1 kA |
|||
C2 Voltage protection level at In |
UP |
160 V |
500 V |
||
C3 Voltage protection level at 1 kV/µs |
UP |
66 V |
290 V |
||
Response time |
tA |
< 30 ns |
|||
Data rate |
|
1 MBit/s |
|||
Series impedance per line |
|
1.5 - 10 Ω |
|||
Parasitic capacitance |
C |
1.5 nF |
|||
Recommended cable cross-section |
|
0.25-1.5 mm2 |
|||
Category tested acc. To IEC 61643-21:2000 |
|
A2, B2, C2, C3, D1 |
![]() |
234/7 Vườn Lài, P. Phú Thọ Hòa,Q.Tân Phú, TP. Hồ Chi Minh |
![]() |
Tel: 028.3978.2976 - 0888.183.943 Fax: 028.3978.2977 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |
![]() |
P.602, S-Home Building, 110A Đường 30/4, Q. Hải Châu, Đà Nẵng |
![]() |
Tel: 023.6384.3554 Fax: 023.6384.3455 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |
![]() |
P.201, 63 Vũ Ngọc Phan, P. Láng Hạ, Q. Đống Đa, TP. Hà Nội |
![]() |
Tel: 024.3775.7157 Fax: 024.3775.7154 |
![]() |
sales@vtech-electric.vn |
![]() |
www.vtech-electric.vn |